XG 50-70kW INVT Three-Phase On-Grid Solar Inverter XG 50-70kW
1. Efficient
* Support over capacity ratio: 1.6X DC input overload
* High energy continuous output: 1.1X AC output overload
* The MPPT efficiency is up to 99.90%
* The lowest starting voltage can reach to 160V
2. Flexible
* Intelligent IV scanning function: it can accurately locate the fault string and make the operation and maintenance more efficient
* 4 MPPT : more flexible string configuration and more choices for installation
* Remote maintenance: support online remote upgrade
* Fan drawer design: 1 minute quick fan replacement
3. Reliable
* IP66
* Input reverse wiring protection, AC short circuit protetion, AC over current protection, Input over voltage protection, Isolation protection, PV string detection, Anti-islanding protection, Over temperature protection, Grounding fault monitoring, ZVRT, Anti-PID function, etc.
4. Intelligent
* Intelligent monitoring: one-stop intelligent operation and maintenance platform for users, providing comprehensive and intuitive power station data monitoring
* Support RS485 / USB / WiFi / GPRS
INVT Inverters
Product Feature
Product Introduction
Model | XG50KTR | XG50KTRL | XG60KTR | XG60KTRL | XG66KTRL | XG70KTRL |
Input (DC) | ||||||
Max. Input Power | 80kW | 96kW | 105.6kW | 112kW | ||
Max. Input Voltage | 1100V | |||||
Start Voltage | 250V | |||||
Rated Input Voltage | 600V | 700V | ||||
Full-load MPP Voltage Range | 520V ~ 850V | 600V-850V | ||||
MPPT Voltage Range | 200V-1000V | |||||
Number of MPPTrackers | 4 | |||||
Number of string per MPPT | 3/2/3/2 | 3Z3/3/3 | ||||
Max. Current per M PPT | 39A/26A/39A/26A | 39A | ||||
Max. Short Circuit Current per MPPT | 48A/32A/48A/32A | 48A | ||||
Output (AC) | ||||||
Max. Output Current | 79.7A | 66.2A | 95.6A | 79.4A | 87.4A | 92.6A |
Rated Output Power | 50kW | 60kW | 66kW | 70kW | ||
Max. Output Power | 55kVA | 66kVA | 72.6kVA | 77kVA | ||
Rated Grid Frequency | 50Hz/60Hz | |||||
Rated Grid Voltage | 230Vac / 400Vac 277Vac / 480Vac 230Vac / 400Vac | 277Vac/ 480Vac | ||||
Power Factor | >0.99 (0.8 leading-0.8 lagging) | |||||
THDi | <3% (Rated Power) | |||||
Efficiency | ||||||
Max. Efficiency |
98.70% 98.80% |
|||||
European Efficiency | 98.40% | 98.50% | ||||
MPPT Efficiency | 99.90% | |||||
Protection | ||||||
DC reverse polarity protection | Yes | |||||
Anti-islanding protection | Yes | |||||
AC short circuit protection | Yes | |||||
Residual current monitoring unit | Yes | |||||
Insulation resistance monitoring | Yes | |||||
Ground fault monitoring | Yes | |||||
Grid monitoring | Yes | |||||
PV string monitoring | Yes | |||||
Surge protection | Type II | |||||
AFCI protection | Optional | |||||
Communication | ||||||
Display | LED/LED+LCD/W 旧+APP | |||||
Communication | Standard: RS485/USB Optional: WiFi/GPRS/Ethernet | |||||
Standard Compliance | ||||||
Grid Connection Standards |
IEC 61727,1 EC 62116, IEC 60068, IEC 61683, VDE-AR-N 4110:2018, VDE-AR-N 4105:2018, VDE-AR-N 4120:2018, EN 50549, AS/NZS 4777.2:2015, CEI 0-21, VDE 0126-1-1/A1 VFR 2014, UTE C15-712-l:2013, DEW A DRRG, NRS 097-2-1, MEA/PEA.C10/11, G98/G99 |
|||||
Safety/EMC General Data | 1 EC 62109-1:2010,1 EC 62109-2:2011, EN 61000-6-2:2005, EN 61000-6-3:2007/Al:2011 | |||||
Dimensions (Wx Hx D) | 650 x 450 x 260 m m | |||||
Weight | 50kg | |||||
Operating Temperature Range | -25°C'+60°C | |||||
Cooling Method | Smart Cooling | |||||
Protection Degree | IP66 | |||||
Max. Operating Altitude | 4000m | |||||
Relative Humidity | 0 ~ 100% | |||||
Topology | Transformerless | |||||
Night Power Consumption | <1W | |||||
Warranty | 5 years (Standard) /10 years (Optional) |